Extra Standard construction with cable tray of the ceiling type

Overview

Example of the Extra Standard construction with cables in a cable tray of the ceiling type- tested with the cables of STRUDER, TECHNOKABEL and DATWYLER.

Fastening with a threaded rod to the ceiling:

  • indirectly to the ceiling with an USOV grip and PSROM10 expandable sleeve bolt;
  • directly with TRSOM10 expandable sleeves - no USOV grip required for a sleeve sunk min. 60 mm into the concrete foundation.

Extra Standard cable tray width:: 400 mm.

Extra Standard spacing of supports: 1,5 m

The load;10 kg/m tested with the cables of STRUDER and TECHNOKABEL. 

Extra Standard load value: 20 kg/m tested with the cables of DATWYLER.

 

    Back to top ↑

    Set elements

    Šírka trasy: Dĺžka nosníka:
    O.no. Product Symbol Item number Pcs in suspension
    1 KCP/KCOP...H60 Cable Tray KCP/KCOP100H60/3 161410
    1
     / 
    3,0 m
    2 LPP/LPOPH60 Straight Connector LPP/LPOPH60 163111
    2
     / 
    3,0 m
    3 BL/BLO... Joint Protection Plate BL/BLO100 100110
    1
     / 
    3,0 m
    4 SGK... Screw Set SGKM6x12 651141
    20
     / 
    3,0 m
    5 WWCT/WWCTO... Bracket WWCT/WWCTO200 713020
    1
     / 
    1,5 m
    6 WPCE/WPCEO... Ceiling Bracket WPCE/WPCEO200 721520
    1
     / 
    1,5 m
    7 PW... Washer PW6 650844
    2
     / 
    1,5 m
    8 PSRO... Anchor Bolt PSROM10x80 804100
    2
     / 
    1,5 m
    9 SGK... Screw Set SGKM6x12 651141
    2
     / 
    1,5 m
    10 SM... Skrutka (komplet) SMM10x120 651443
    1
     / 
    1,5 m
    11 BR.../1 Spacer BR61/1 707021
    1
     / 
    1,5 m
    Add selected to the project Add all to the project
    Specify cable channel length [m]:
    Calculate
    Back to top ↑

    Examples

    Example of the Extra Standard construction with cables in a cable tray of the ceiling type- tested with the cables of STRUDER, TECHNOKABEL and DATWYLER.

    Extra Standard cable tray width- 400mm.

    Extra Standard spacing of supports- 1,5m.

    Extra Standard load value- 20 kg/m ? tested with the cables of DATWYLER.

    Fastening with a threaded rod to the ceiling;

    • indirectly with an USOV grip and PSROM10 expandable sleeve bolt to the ceiling.
    • directly with theTRSOM10 expandable sleeves - no USOV grip required for a sleeve sunk min. 60 mm into the concrete foundation.
    Back to top ↑